Toshiba PROSEC T1 User Manual page 304

Programmable controller
Hide thumbs Also See for PROSEC T1:
Table of Contents

Advertisement

10. Troubleshooting
Error message and related information
Event
Illegal inst
Illegal sys intrpt
Invalid Fun inst
Invalid program
Loop nesting error
Memory full
No END/IRET error
No RET error
No sub-r entry
302
T1/T1S User's Manual
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Info 1
Info 2
Info 3
Program
Address
type -
in the
block No.
block
Interrupt
Interrupt
address 1
address 2
Program
Address
Fun No.
type -
in the
block No.
block
Program
type -
block No.
Program
Address
type -
in the
block No.
block
Program
Address
type -
in the
block No.
block
Program
Address
Sub-r No.
type -
in the
block No.
block
Program
Address
Sub-r No.
type -
in the
block No.
block
Special
Meaning and countermeasures
device
S006
An illegal instruction has been detected in the
S030
program. (Error down)
S060
Reload the program and execute EEPROM
write operation again.
Unregistered interrupt has occurred. (No
error down)
If the error occurs frequently, replace the unit.
A function instruction which is not supported
by the T1/T1S is programmed. (Error down)
Correct the program.
A basic ladder instruction which is not
supported by the T1/T1S is programmed.
(Error down)
Correct the program.
SUBR instruction is not programmed before
RET instruction. (Error down)
Correct the program.
An abnormality is detected in the program
management information. (Error down)
Reload the program and execute EEPROM
write operation again.
A FOR-NEXT loop is programmed inside
other FOR-NEXT loop. (Error down)
Correct the program.
The program exceeds the executable
memory capacity. (Error down)
Reduce the program steps.
The END instruction is not programmed in
the main program or in the sub-program.
(Error down)
Correct the program.
The IRET instruction is not programmed in
the interrupt program. (Error down)
Correct the program.
The RET instruction is not programmed in the
subroutine program. (Error down)
Correct the program.
The subroutine corresponding to CALL
instruction is not programmed. (Error down)
Correct the program.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Prosec t1s

Table of Contents