Real-Time Data Link System - Toshiba PROSEC T1 User Manual

Programmable controller
Hide thumbs Also See for PROSEC T1:
Table of Contents

Advertisement

1. System Configuration

1.8 Real-time data link system

TOSLINE-F10
TOSLINE-F10 is a high speed data transmission system suited for small points I/O
distribution system. By inserting the TOSLINE-F10 remote card (FR112) into the T1-
40/T1-40S, the T1-40/T1-40S can work as a remote station of the TOSLINE-F10
network. On this network, the T1-40/T1-40S sends 1 word data to the master station
and receives 1 word data from the master station.
Topology
Transmission distance
(without repeater)
Transmission speed
Scan transmission
capacity
Scan cycle
Error checking
NOTE
Typical data link configuration
The figure below shows the typical data link configuration.
T1-40(S)
36
T1/T1S User's Manual
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Item
Bus (terminated at both ends)
500 m max. (total)
750 kbps
512 points (32 words) max.
7 ms/32 words
CRC check
(1) Refer to the separate "T1 User's Manual - Option Card and I/O
Module -" for details of the TOSLINE-F10 remote card (FR112).
(2) Refer to the separate TOSLINE-F10 User's Manual for details of overall
TOSLINE-F10 system.
TOSLINE-F10
T1-40(S)
T1-40(S)
Operator interface units
TOSLINE-F10 system specifications
High speed mode
Master
computer
T2E
(master)
T2E
(remote)
Long distance mode
1 km max. (total)
250 kbps
12 ms/32 words
RI/O
RI/O
RI/O: remote I/O
6F3B0250

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Prosec t1s

Table of Contents