FUN 101
Expression
Input -[ A <= B ]- Output
Function
When the input is ON, the data of A and the data of B are compared, and if A is less than or equal to
B , the output is turned ON.
Execution condition
Input
OFF
No execution
ON
Execution
Operand
Name
A Compared
data
B Reference data
Example
When R00C is ON, the data of D0125 is compared with the constant data -100, and if the data of
D0125 is less than or equal to -100, R020 is turned ON.
If the data of D0125 is -150, the comparison result is true. Consequently, R020 is turned ON.
D0125
-150
If the data of D0125 is 0, the comparison result is false. Consequently, R020 is turned OFF.
D0125
Note
· This instruction deals with the data as signed integer (-32768 to 32767).