7. Instructions
FUN 096
Expression
Input -[ A > B ]- Output
Function
When the input is ON, the data of A and the data of B are compared, and if A is greater than B , the
output is turned ON.
Execution condition
Input
OFF
No execution
ON
Execution
Operand
Name
A Compared
data
B Reference data
Example
When R00C is ON, the data of D0125 is compared with the constant data 2500, and if the data of
D0125 is greater than 2500, R020 is turned ON.
If the data of D0125 is 3000, the comparison result is true. Consequently, R020 is turned ON.
D0125
3000
If the data of D0125 is -100, the comparison result is false. Consequently, R020 is turned OFF.
D0125
-100
Note
· This instruction deals with the data as signed integer (-32768 to 32767).
196
T1/T1S User's Manual