FUN 165
Expression
Input -[ A FG ( n ) B ® C ]- Output
Function
When the input is ON, this instruction finds the function value f(x) for A as x, and stores it in C . The
function f(x) is defined by the parameters stored in 2 ´ n registers starting with B .
Execution condition
Input
OFF
No execution
ON
Execution
Operand
Name
A Input value x
n Parameter size
B Start of
parameters
C Function value
f(x)
Example
When R010 is ON, the FG instruction finds the function value f(x) for x = XW004, and stores the
result in D0100.
The function f(x) is defined by 2 ´ 4 = 8 parameters stored in D0600 to D0607. In this example,
these parameters are set at the first scan.
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
FG
Function generator
Operation
Device
X
Y
R
S
T.
C. XW YW RW SW T
Output
OFF
ON
Register
C
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Ö
Basic Hardware and Function
6F3B0250
7. Instructions
Constant Index
D
I
J
K
Ö
Ö
Ö
Ö
Ö
1 - 32
Ö
Ö
Ö
Ö
Ö
247