Managing The Users; Tools Section; Data Log Status; Rs 485 Test - Emerson Dixell X-web300 Operation Manual

Hide thumbs Also See for Dixell X-web300:
Table of Contents

Advertisement

button.

3.9.1 MANAGING THE USERS

You can interact with a user in 3 different ways:
Setting-up permission.
Disabling the user (Enabling check box on the top right corner).
Modify account and password

3.10 TOOLS SECTION

XWEB has a complete set of useful tools to help the user managing in the best way both the monitoring unit
and the controllers connected on the RS 485. Click on "Tools" menu to start using it.

3.10.1 DATA LOG STATUS

One of the most important tools is the "Data log Status". This window gives you important information
concerning the available amount of memory reserved to store data values. Value "Log" followed by a
percentage is the amount of used memory at the present moment. XWEB will give you a forecast expressed
in days/hours on the duration of the stored data starting back from the last recorded value. The archive is in
FIFO format, so the first data (the oldest one) is also the first to be overwritten. To enlarge this recording time
you can decide which values you really need to store. To do this please click on "Configuration" -> "Devices"
roll-down menu and select a controller. At this point uncheck all the value you do no want to record. In the
following example DI "Defrost Start" is shown but not recorded.

3.10.2 RS 485 TEST

It is possible to make a test on the RS 485 line. Click on "RS 485". The following window will appear: