Instead of "xxx_New_Model" the user can insert the new appropriate name for this instrument.
3.3.6.2

ASSIGN THE NAME OF THE CONTROLLER

After selecting the device, click into the "Name" field. Insert the new name such as "Frozen food_001".
Assign the proper sampling "Interval", decide if you want to read and record data from this instrument by
checking/unchecking "Data Reading" and "Recording" boxes.
"Data Buffer" is an useful function that stores with the maximum speed available lots of data values
(regardless of sampling interval) when an alarm occurs. Ten minutes of data values before and 5 after
the alarm are recorded at maximum speed if "Data Buffer" box is checked. Finally if you need to
synchronize the on-board RTC of the controller, select RTC.
Click "Modify" now or at the end of the whole configuration.
3.3.6.3

ASSIGN THE CATEGORY TO THE DEVICE "DEVICE CATEGORY SETUP"

Be sure of having selected the right instrument under the "Device" menu.
Depending on the instrument model there are different available categories to define the attributes of the
instrument itself. If you do not find the right one maybe it is not defined or it is not available for that
instrument. By itself XWEB, after the recognising procedure, assigns the default categories (if you
checked the box in category window) to the devices connected to the RS 485. To change the category
click inside the field and select the appropriate item.
Click "Modify" now or at the end of the whole configuration.
3.3.6.4

ASSIGN THE ALARM TYPOLOGY

Be sure of having selected the right instrument under the "Device" menu.
ALARM ORIGIN: depending on the instrument model there are different available alarms, if you do not
find the right one it means that it is not available for that instrument.
NAME: each alarm can be assigned with an appropriate label defined by the user, this label is also used
when it is displayed by the system. Click inside the "Name" and modify it.
TIPOLOGY: links alarm type to the proper Alarm typology.
If you do not find the proper action in it, step back to the Alarms definition to insert the new features into
a new alarm typology.
SH (Show): when it is enabled th alarm is showed in main page.
SND (Send): when it is enabled the alarm is sent by XWEB.
REC (Recording): when it is enabled the corresponding alarm is logged.
Click "Modify" now or at the end of the whole configuration.