2.1.2 SERIAL ADDRESS
The cable must have 2 or 3 wires with shield, minimum section 0,5mm
From the XWEB position the cable reaches all the instrument positions.
Do not execute loops or derivations:
Right connection
Wrong connection
Do not connect shield to ground.
Do not connect the "Gnd" terminal.
Remember to draw a map of the line. This will help you to find an error if something is wrong.
The instrument with RS485 have "+" and "
To keep the line balanced it is necessary a 120 Ohm resistor at the end of the line (you can use the RS
485+ and RS 485- terminals of the last instrument connected).
2.1.3 THE TTL OUTPUT
1592028000 XWEB300D_500_500D opr GB r2.2.0 2013.08.01.docx
-
" terminals, respect the polarity.
XWEB500/300
(e.g. the BELDEN 8772).