2.2.1.2
VIEW MENU
By pressing VIEW the following options are available:
->
Data
Alarm
Tools
Data is to browse the current/recorded temperatures
Alarm is to browse the current/recorded alarms
Tools let you start the RS485 line test
2.2.1.2.1
MODIFY SETPOINT
By using Data menu, then actual, it is possible to modify the setpoint of a controller. This is the view layout:
->
Name of the controller
>---A-INPUT---------<
Air Temperature: 4.20°C
>---SETPOINT---------<
Set point: 4°C
>---D-INPUT---------<
Open door: OFF
Generic alarm: OFF
>---STATUS---------<
ON/OFF: ON
Defrost: OFF
>---OUTPUT---------<
Defrost: OFF
Fan: OFF
Compressor: ON
>---ALARM ---------<
High Temperature: OFF
Low Temperature: OFF
Generic alarm: ON
>---COMMANDS---------<
OFF
ON
DEFROST
...
>---A-INPUT---------< means analog inputs (probes)
>---SETPOINT---------< setpoint
>---D-INPUT---------< means digital input
>---STATUS---------< reports the status of the controller
>---OUTPUT---------< reports the outputs staus of the controller
>---ALARM---------< current alarm list
>---COMMAND---------< current command list
To modify the setpoint move the marker "->" to highlight the actual setpoint and modify it by pressing
ENTER. Increse/decrease the current value by means of the up/down arrow keys. Press ENTER to confirm
To send a command, scroll the list until you reach the section >---COMMANDS---------<, select the command
and press ENTER. To confirm press ENTER again.
1592028000 XWEB300D_500_500D opr GB r2.2.0 2013.08.01.docx
XWEB500/300
21/114