Lenovo ThinkServer RD220 Hardware Maintenance Manual page 92

Hardware maintenance manual for rd220
Hide thumbs Also See for ThinkServer RD220:
Table of Contents

Advertisement

Table 3. DSA diagnostic messages (continued)
• Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved.
• See Chapter 7 "Parts listing, ThinkServer RD220 Type 3729, 3779, 3797, and 3798" on page 205 to determine
which components are customer replaceable units (CRU) and which components are field replaceable
units (FRU).
• If an action step is preceded by "(Trained service technician only)," that step must be performed only by
a trained service technician.
Message
number
Component
166-919-xxx
RMM
86
ThinkServer RD220 Hardware Maintenance Manual
Test
State
Description
12C Test
Failed
The RMM
indicates a
failure in the
memory card
1 light path
diagnostics
bus.
Action
1. Turn off the system and disconnect
it from the power source. You must
disconnect the system from ac power to
reset the RMM.
2. After 45 seconds, reconnect the system
to the power source and turn on the
system.
3. Run the test again.
4. Make sure that the DSA code
is at the latest level. For the
latest level of DSA code, go to
http://www.ibm.com/support/docview.wss?uid=psg1SERV-D
5. Make sure that the RMM firmware
is at the latest level. The installed
firmware level is shown in the DSA
event log in the Firmware/VPD
section for this component. For
the latest level of firmware, go to
http://www.ibm.com/support/docview.wss?uid=psg1
MIGR-4JTS2T and select your system to
display a matrix of available firmware.
6. Run the test again.
7. Turn off the system and disconnect it
from the power source.
8. Reconnect the system to the power
source and turn on the system.
9. Make sure that the reported memory size
is the same as the installed memory size.
10. If the problem remains, replace the
memory card in memory-card connector
1.