Levelflex FMP56, FMP57 HART

Switch-on delay

Navigation
Prerequisite
Description
User entry

Switch-off value

Navigation
Prerequisite
Description
User entry
Additional information
Endress+Hauser
A
Switch-on value
B
Switch-off value
C
Output closed (conductive)
D
Output opened (non-conductive)
 Setup → Advanced setup → Switch output → Switch-on delay
• Switch output function (→  150) = Limit
• Assign limit (→  151) ≠ Off
Defines the delay applied before the output is switched on.
0.0 to 100.0 s
 Setup → Advanced setup → Switch output → Switch-off value
Switch output function (→  150) = Limit
Defines the switch-off point.
The output is opened if the assigned process variable falls below this point.
Signed floating-point number
The switching behavior depends on the relative position of the Switch-on value and
Switch-off value parameters; description: see the Switch-on value parameter
(→  152).