Levelflex FMP56, FMP57 HART
Selection
Additional information
Value current output 1 to 2
Navigation
Prerequisite
Description
User entry
Additional information
Switch output simulation
Navigation
Description
Selection
Switch status
Navigation
Prerequisite
Description
Selection
Additional information
Endress+Hauser
• Off
• On
An active simulation is indicated by a diagnostic message of the Function check (C)
category.
Expert → Diagnostics → Simulation → Value curr.out 1 to 2
Current output simulation (→ 182) = On
Defines the value of the simulated output current.
3.59 to 22.5 mA
The current output assumes the value specified in this parameter. In this way, users can
verify the correct adjustment of the current output and the correct function of connected
control units.
Expert → Diagnostics → Simulation → Switch sim.
Switch the simulation of the switch output on and off.
• Off
• On
Expert → Diagnostics → Simulation → Switch status
Switch output simulation (→ 183) = On
Current status of the switch output.
• Open
• Closed
The switch status assumes the value defined in this parameter. This helps to check correct
operation of connected control units.