Levelflex FMP56, FMP57 HART
Endress+Hauser
due to a level change during operation. Signals which are already in the blocking distance
when the device is switched on, are ignored.
This behavior is only valid if the following two conditions are met:
• Expert → Sensor → Echo tracking → Evaluation mode = Short time history or Long
time history)
• Expert → Sensor → Gas phase compensation → GPC mode= On, Without correction
or External correction
If one of these conditions is not met, signals in the blocking distance will always be
ignored.
A different behavior for signals in the blocking distance can be defined in the
Blocking distance evaluation mode parameter.
If required, a different behavior for signals in the blocking distance can be defined by
the Endress+Hauser service.
 55
Blocking distance (UB) for bulk solid measurements
UB
Operating menu
A0013221
139