Operating menu
Switch-off delay
Navigation
Prerequisite
Description
User entry
Failure mode
Navigation
Prerequisite
Description
Selection
Additional information
Switch status
Navigation
Description
Invert output signal
Navigation
Description
Selection
154
 Setup → Advanced setup → Switch output → Switch-off delay
• Switch output function (→  150) = Limit
• Assign limit (→  151) ≠ Off
Defines the delay applied before the output is switched off.
0.0 to 100.0 s
 Setup → Advanced setup → Switch output → Failure mode
Switch output function (→  150) = Limit or Digital Output
Defines the state of the switch output in case of an error.
• Actual status
• Open
• Closed
 Setup → Advanced setup → Switch output → Switch status
Current status of the switch output.
 Setup → Advanced setup → Switch output → Invert outp.sig.
' N o'
The switch output behaves as per its parameter setting.
' Y es'
The switching behavior is inverted as compared to its parameter setting.
• No
• Yes
Levelflex FMP56, FMP57 HART