3G-SC200 Data-Voice-Video Power Solutions Installation Guide
Notes
AVC must be enabled. Allow up to 1 minute for the system to stabilize after load or
1
voltage changes.
Breathing on the sensor can increase the temperature.
2
Battery Current Limit control function may have to be turned off to allow the Fast
3
Charge voltage to reach its value within the 1 minute test duration.
Refer to Generator Start Option for details.
4
There may be slight current fluctuations above and below the configured current limit
5
setting. This can be due to the current control within the factory preset deadband.
Confirmation of this control function may be witnessed in the Fast Charge test.
There may be a delay of up to 2 minutes before the currents stabilize between rectifiers.
6
There may be a delay of up to 10 seconds before the LVD changes state.
7
APS systems may not display a Manual Connect alarm on the SC200 if the system
voltage is above the LVD disconnect voltage.
Perform the test on each LVD control module within the system.
For manual LVD operation see details.
For an explanation of LVD LED indications see Troubleshooting on page 44.
84