Dip Switch Settings - Omron K8DT-LS Series Manual

Conductive level controller
Table of Contents

Advertisement

Nomenclature
Front Panel
Terminal block
(See note.)
Power indicator
Output status indicator
Terminal block
(See note.)
Note: Use solid wires, stranded wires, or ferrules to connect to the
terminals.
To maintain the withstand voltage after connecting the
terminals, insert 8 mm of exposed conductor into the terminal.
Solid Wire
Stranded Wires
8 mm
Operation Method
Connections
Outputs
For a relay output, the SPDT contacts are output on terminals 11, 12, and 14. For a transistor output, the output is on terminals 11 and 14.
The internal circuit of the transistor output is NPN, but application is possible for either a sinking or sourcing output.
In the case of sinking output applications
14
load
Sinking
11
K8DT

DIP Switch Settings

The operating mode is set using the DIP switch located on the front of the Unit.
K8DT-LS does not use SW2, SW3 and SW4.
Note: Open the DIP switch cover to set the DIP switch.
Keep the DIP switch cover closed while the power supply to the Relay is ON.
SW4
SW3
DIP switch pins
SW2
SW1
Operating resistance knob
Operating time knob
Ferrules
8 mm
8 mm
In the case of sourcing output applications
14
Sourcing
11
K8DT
DIP Switch Function
Pin
Operating mode
Note: All pins are set to OFF by default.
Indicators
Item
Power indicator (PWR:
Green)
Output status indicator
(Output: Yellow)
Setting Knobs
Item
Operating resistance knob
Operating time knob
load
❍ ↑
1
ON
ON
● ↓
OFF
OFF
Automatic liquid
discharge
operation
Automatic liquid
supply operation
K8DT-LS
Description
Lit when power is being supplied.
Lights for output.
Description
Used to set the resistance to 10 k to
100 kΩ.
Used to set the operating time to 0.1 to
10 s.
2
3
Not used.
Not used.
Not used.
4
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

K8dt-ls1cdK8dt-ls1tdK8dt-ls1caK8dt-ls1ta

Table of Contents