7-2

CompoWay/F Slaves Connected to a PLC

7-2-1
Communications with CompoWay/F Slaves through a PLC
Use the following procedures to transfer network information of CompoWay/F Slaves
connected to a serial port of a CS/CJ-series CPU Unit or Serial Communications
Board/Unit, or serial port C on the Controller Section of an NSJ-series NSJ Controller.
Example: In the following example, an E5CN Temperature Controller is connected to
Before Connecting by CompoWay/F Protocol
Before connecting by the CompoWay/F protocol, edit the CJ1W-SCU41-V1 Unit's
parameters to set the serial port 1 Serial communications mode to Serial Gateway.
1. Right-click the Serial Communications Unit in the I/O table and select Unit Setup.
The Edit Parameters Dialog Box will be displayed.
2. Set the Port1: Port settings set value to User settings.
3. Set the Port1: Serial communications mode set value to Serial Gateway.
7-2
7-2-1
Communications with CompoWay/F Slaves through a PLC
port 1 (RS-422/RS-485 port) of a CJ1W-SCU41-V1 Serial
Communications Unit with the CompoWay/F protocol.
Example: Unit settings for a Serial
Communications Unit/Board
CompoWay/F Slaves Connected to a PLC
2. Set to User settings.
3. Set the Serial communications mode
to Serial Gateway.
7-3