Uploading
Network
PLC
The network configuration of another PLC can be read via the PLC that was first
connected to the computer (known as the relay PLC). To read another PLC's network
configuration, switch the target PLC from the relay PLC to the desired PLC connected.
At this point, it is possible to upload the configuration of the network (including
component parameters) of the network connected to that target PLC.
Note: When accessing a target PLC other than the relay PLC, observe the following two pre-
cautions, set routing tables, and transfer them to the PLCs.
• Always create local network tables and transfer them to the relay PLC and target PLC.
• When specifying a target PLC in another network, register both local network tables and
relay network tables in all of the PLCs on the path between the relay PLC and target PLC.
Overall Procedure
Start the CX-Integrator.
Connect online to the relay PLC.
Create the local network table.
Transfer the local network table to the relay
PLC via the serial connection.
Connect to a Communications
Unit/port to enable accessing it.
Upload the network structure.
Switch the target PLC.
Connect to a Communications
Unit/port to enable accessing it.
Upload the network structure.
Configurations from Target PLCs other than the Relay
Example: Select Component − Auto
Online from the menu bar to automatically
connect online using a serial connection.
Create the local network tables
Required when there is
and relay network tables.
more than one Network
Communications Unit in
the relay PLC.
Transfer the routing tables to all PLCs
between the relay PLC and target PLC.
Right-click the desired network in the Online
Connection Information Window and select
Connect from the pop-up menu.
Right-click the target PLC in the
Network Structure Window and select
Connect to this PLC.