Omron CX-INTEGRATOR - V1.1 Operation Manual page 162

Table of Contents

Advertisement

8 Set node address 02 as shown in the following table.
Item
Node address
PLC type
Area 1
Memory area
Start address
Send size
Area 2
Memory area
Start address
Send size
Ordered destination nodes
Data link status
Memory area
start address
Start address
9 Set node address 03 as shown in the following table, and then click the Next
Button or press the Enter key.
Item
Node address
PLC type
Area 1
Memory area
Start address
Send size
Area 2
Memory area
Start address
Send size
Ordered destination nodes
Data link status
Memory area
start address
Start address
4-3
Manually Setting Data Links
4-3-4
Creating Data Link Tables Offline
Data set
2
CS1G-
CPU45
CIO
Sets CIO 1200 as the data link start
address for the Area 1 local node.
1200
30
Sets 30 words as the send size (unit:
words) for the Area 1 local node.
D
Sets D00600 as the data link start
address for the Area 2 local node.
600
30
Sets 30 words as the send size (unit:
words) for the Area 2 local node.
1, 2, 3
Specifies the node refresh sequence.
Beginning with the start addresses,
nodes 01, 02, and 03 are set in order.
(Reception from node 01 is first,
followed by transmission from the local
node, and finally reception from node
03.)
CIO
Sets CIO 1300 as the data link status
start address.
1300
Data set
3
CS1G-
CPU45
IR
Sets IR 300 as the data link start
address for the Area 1 local node.
300
40
Sets 40 words as the send size (unit:
words) for the Area 1 local node.
DM
Sets DM 700 as the data link start
address for the Area 2 local node.
700
40
Sets 40 words as the send size (unit:
words) for the Area 2 local node.
2, 1, 3
Specifies the node refresh sequence.
Beginning with the start addresses,
nodes 02, 01, and 03 are set in order.
(Reception from node 02 is first,
followed by reception from node 01, and
finally transmission from the local node
address.)
LR
Sets LR0 as the data link status start
address.
0
Description
Description
4-15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cx-integrator 1.1Sysmac cxone-al**c-e