Handling Precautions; Procedure For Replacing A Pcu; Pcu Parameters And Operating Data Set In Cpu Unit's Dm Area - Omron CJ1W-C113 - REV 02-2008 Operation Manual

Position control units
Table of Contents

Advertisement

Handling Precautions

No.
Item
3
Installation and
wiring
Required Tools

12-3 Handling Precautions

12-4 Procedure for Replacing a PCU

12-4-1 PCU Parameters and Operating Data Set in CPU Unit's DM Area

1,2,3...
Inspection points
Is the PCU securely mounted?
Are the cable connectors properly
inserted and locked?
Are there any loose screws in the exter-
nal wiring?
Are any external cables disconnected?
The following tools, materials, and equipment are required when performing
an inspection.
Phillips screwdriver
Voltage tester or digital voltage meter
Industrial alcohol and a clean cotton cloth
The following measuring devices may be required when performing an
inspection.
Synchroscope
Pen oscilloscope
Thermometer
Hydrometer
• Turn OFF the power before replacing the PCU.
• If a PCU is found to be faulty and is replaced, check the new PCU again to
ensure there are no errors.
• When returning a faulty PCU for repair, make a detailed record of the
PCU's malfunction and take it together with the PCU to your nearest
OMRON office or sales representative.
• If a contact is not good, put some industrial alcohol on a clean cotton cloth
and wipe the surface. After doing this, install the PCU.
Use the following procedure when it is necessary to replace a PCU.
1. Make a note of the unit number of the PCU to be replaced.
2. Save the parameters and operating data for the PCU to be replaced to a
floppy disk or a hard disk using, for example, CX-Programmer.
3. Turn OFF the power supply.
4. Make a note of the way in which the PCU is wired. (It is recommended that
the cables are labelled.)
5. Replace the PCU, and reconnect the wiring as before.
6. Set the unit number for the PCU.
7. Turn ON the power supply to the PLC.
8. Transfer the saved parameters and operating data to the CPU Unit using,
for example, CX-Programmer.
9. Turn the PLC power OFF and back ON.
Criteria
There must be no loose-
ness.
There must be no exter-
nal abnormalities.
Section 12-3
Remarks
Lock the sliders securely.
Carefully insert and lock
all cable connectors.
With a Phillips screw-
driver, tighten all screws
in the external wiring.
Do a visual check and
connect or replace cables
as required.