Omron CJ - REFERENCE MANUAL 02-2010 Reference Manual page 79

Table of Contents

Advertisement

Instruction
Symbol/Operand
Mnemonic
Code
MULTI-OUTPUT
MTIM(543)
TIMER
MTIM
543
(BCD)
MTIMX
554
D1: Completion
(Binary)
Flags
(CJ2, CS1-H,
D2: PV word
CJ1-H, CJ1M, or
S: 1st SV word
CS1D only)
MTIMX(554)
D1: Completion
Flags
D2: PV word
S: 1st SV word
COUNTER
Count
CNT
input
CNT
(BCD)
CNTX
Reset
546
input
(Binary)
N: Counter
(CJ2, CS1-H,
number
CJ1-H, CJ1M, or
S: Set value
CS1D only)
Count
CNTX(546)
input
Reset
input
N: Counter
number
S: Set value
CS/CJ/NSJ Series Instructions Reference Manual (W474)
MTIM(543)/MTIMX(554) operates a 0.1-s incrementing timer with 8
independent SVs and Completion Flags. The setting range for the
D1
set value (SV) is 0 to 999.9 s for BCD and 0 to 6,553.5 s for binary
(decimal or hexadecimal).
D2
S
to
D1
D2
Timer input
S
Timer PV (D2)
Completion
Flags (D1)
CNT/CNTX(546) operates a decrementing counter. The setting range
for the set value (SV) is 0 to 9,999 for BCD and 0 to 65,535 for binary
N
(decimal or hexadecimal).
S
Count input
Reset input
Counter PV
N
Completion
S
Flag
Function
Timer PV
Timer SVs
to
SV 7
SV 2
SV 1
SV 0
0
Bit 7
to
Bit 2
Bit 1
Bit 0
SV
2. Summary of Instructions
Location
Execution
condition
Output
Required
0
Output
Required
Page
238
2
242
43

Advertisement

Table of Contents
loading

Table of Contents