Omron CJ - REFERENCE MANUAL 02-2010 Reference Manual page 264

Table of Contents

Advertisement

3. Instructions
• When TIMU(541)/TIMUX(556) is in a program section between IL(002) and ILC(003) and the
program section is interlocked, the PV will be reset to the SV and the Completion Flag will be turned
OFF.
• TIMU(541)/TIMUX(556) timers may not time accurately when used in a program section jumped by
the JMP(004), CJMP(510), CJPN(511), and JME(005) instructions.
• When a TIMU(541)/TIMUX(556) timer is forced set, its Completion Flag will be turned ON. When a
TIMU(541)/TIMUX(556) timer is forced reset, its Completion Flag will be turned OFF.
• If online editing is used to overwrite a timer instruction, always reset the Completion Flag. The timer
will not operate properly unless the Completion Flag is reset.
Example Programming
When timer input CIO 0.00 goes from OFF to
ON in this example, the timer PV will begin
counting down. The Timer Completion Flag,
T0000, will be turned ON after 12.3 ms.
When CIO 0.00 goes OFF, the Timer
Completion Flag, T0000, will be turned OFF.
228
0.00
TIMU
or
0.00
CS/CJ/NSJ Series Instructions Reference Manual (W474)
#0123
TIMUX
&0123

Advertisement

Table of Contents
loading

Table of Contents