2. Summary of Instructions
2-2-4

Timer and Counter Instructions

Instruction
Symbol/Operand
Mnemonic
Code
TIMER RESET
TRSET(549)
TRSET
@TRSET
549
N: Timer number
(CJ2 only)
HUNDRED-MS
TIMER
TIM
(BCD)
TIMX
N: Timer number
(Binary)
S: Set value
(CJ2, CS1-H,
CJ1-H, CJ1M, or
CS1D only)
TIMX(550)
N: Timer number
S: Set value
TEN-MS TIMER
TIMH(015)
TIMH
015
(BCD)
TIMHX
N: Timer number
551
S: Set value
(Binary)
(CJ2, CS1-H,
CJ1-H, CJ1M, or
TIMHX(551)
CS1D only)
N: Timer number
S: Set value
40
Resets the specified timer.
N
TIM/TIMX(550) operates a decrementing timer with units of 0.1-s.
TIM
The setting range for the set value (SV) is 0 to 999.9 s for BCD
N
and 0 to 6,553.5 s for binary (decimal or hexadecimal).
S
Timer input
Timer PV
Completion
Flag
N
S
Timer input
Timer PV
Completion
Flag
TIMH(015)/TIMHX(551) operates a decrementing timer with units of
10-ms. The setting range for the set value (SV) is 0 to 99.99 s for BCD
and 0 to 655.35 s for binary (decimal or hexadecimal).
N
S
Timer input
Timer PV
Completion
N
Flag
S
Timer input
Timer PV
Completion
Flag
Function
SV
SV
SV
SV
CS/CJ/NSJ Series Instructions Reference Manual (W474)