Error messages

Grey background means that the automatic control unit must be restarted (power off) in order to reset the error message.
Error
code
Not an error code – indicates the type of EP104
EP-1
in use
Not an error code – indicates the type of EP104
EP-2
in use
No error, shown to acknowledge a change in the
E000
service channel.
E003
Limited running time exceeded
E008
Momentary loss of 24 V
E015
Momentary loss of 230V
Safety edge or load guard triggered five times in
E017
succession
E020
Voltage too high in safety circuit
E025
Incorrect setting for personal protection, motor 1
E026
Incorrect setting for personal protection, motor 2
Incorrect setting for motor protection, low limit
E027
inactive
E028
Brake selected when using a frequency converter
E032
Limit switch L.O1 has lost its position
E033
Limit switch L.C1 has lost its position
E034
Limit switch L.O2 has lost its position
E035
Limit switch L.C2 has lost its position
E040
Invalid selection in the service channel
E044
Hidden channels shown
E046
Opening counter reset
E047
Factory reset of all channels
E048
Error code list reset
Unknown circuit board, EP104 or Light not fully
E050
equipped
Incorrect software, full version programmed in
E051
EPLight
Incorrect software, EPLight software programmed
E052
into a fully equipped EP104
E116
No safety edge acknowledgement
E201
Motor protection triggered for motor 1
E202
Motor protection triggered for motor 2
78
Meaning
Possible cause
Gears slipping? Check C403
Mains failure, momentary 24 V short circuit.
Has there been a power failure?
It something preventing the door reaching the closed
position?
The voltage measured by the automatic control unit is too
high.
Check C200 and C230, the load guard cannot be disabled
with personal protection activated. Check C211, it cannot
be longer than 0.06 seconds. C212 cannot be longer than 2
seconds. C493 cannot be longer than 0.20 seconds.
Check C200 and C240, the load guard cannot be disabled
with personal protection activated. Check C211, it cannot
be longer than 0.06 seconds. C212 cannot be longer than 2
seconds. C493 cannot be longer than 0.20 seconds.
If C202 is not set to 4 C201 may not be set to 1. C201 is
only used with a frequency converter.
Check that C495 is set to 0.
Is the limit switch cam bypassing the switch? Loose
connection in switch?
Is the limit switch cam bypassing the switch? Loose
connection in switch?
Is the limit switch cam bypassing the switch? Loose
connection in switch?
Is the limit switch cam bypassing the switch? Loose
connection in switch?
Contact FAAC Nordic AB
Contact FAAC Nordic AB
Contact FAAC Nordic AB
Only applies to up-and-over control, fault in safety edge?
Correct run-on time?
Motor is taking more than 1.5x motor current. Motor is
sluggish or stops. Faulty fuse? Phase failure in an incoming
phase? Break in cable to motor or motor winding? Check the
motor protection setting.