Safety Edge - DAAB EP104 Instruction Manual

Automatic control unit
Hide thumbs Also See for EP104:
Table of Contents

Advertisement

DAAB AUTOMATIC CONTROL UNIT EP104

Safety edge

No.
Name
C101
Safety edge acknowledgement S.E1
0
Disabled
1
Enabled
C102 Function of output for external protection
S
0
Check disabled, open output.
1
Closed to GND on activation, normally open.
2
Closed to +24 VDC on activation, normally open.
3
Open on activation, normally closed to GND.
4
Open on activation, normally closed to +24 VDC.
C103 Function of safety edge input during test of external
S
safety edge unit
1
Low resistance during test
2
High resistance during test
C105
Low speed or activated safety edge
(Only when using a frequency converter)
0
Disabled
1
Active
C111 Selects function for safety edge S.E1
S
0
S.E1 disabled
1
Limits according to set value in C115
2
Fixed limits between 5 kohm and 15 kohm
C112 Reverse/stop with activated safety edge S.E1
S
1
Reverse
2
Stop
C113 Check of external protection connected to S.E1
S
0
No check
1
Test of protection connected to S.E1
C114
Impedance readout S.E1
Set impedance value for safety edge S.E1
C115
Set to 1 only at C111.
C121 Selects function for safety edge S.E2
S
0
S.E2 disabled
1
Limits according to set value in C125
2
Fixed limits between 5 kohm and 15 kohm
C122
Reverse/stop with activated safety edge S.E2
1
Reverse
2
Stop
C123 Check of external protection connected to S.E2
S
0
No check
1
Test of protection connected to S.E2
C124
Impedance readout S.E2
Bruksanvisning utgåva 1 för Programversion 4.06
Range
Factory Setting Ref.
0 – 1
0
0 – 4
0
1 – 2
1
0 - 1
0
0-2
2
1 - 2
1
0 - 1
1
00.0-99.9 kΩ
1.0-9.9 kΩ
8.2
0-2
2
1 – 2
1
0 - 1
1
00.0-99.9 kΩ
page