DAAB AUTOMATIC CONTROL UNIT EP104
Safety edge function in the closing movement
On delivery and after a reset, the EP104 is configured to reverse to the fully open position when the safety edge is activated
in the closing movement.
Safety edge function in the opening movement
On delivery and after a reset, the EP104 is configured to reverse when the safety edge is activated in the opening movement.
Reverse does not take place to the closed position, but according to the time specified in C494.
Set the reverse function with the value 1 in channel C132, and specify the delay in channel C493.
Low speed after safety edge activation (Only when using a frequency converter)
Using this setting one can let the gate close slowly if it has reversed due to a safety edge. This is to prevent it closing on any
remaining obstacle with full force. Set C105 either to 0 to deactivate the function or 1 to activate it, remember that this is
only possible when using a frequency converter.
Performance testing safety edges
Check that the automatic control unit reacts as intended as configured above when the safety edge is activated.
Check that the LEDs indicate activated safety edges S.E1, S.E2 and S.E3 with a constant light. Also check that the safety
edges flash when they are no longer activated.
Bruksanvisning utgåva 1 för Programversion 4.06