Programmable Inputs, P Channels; Automatic Closing; Configuring Automatic Closing; Stop Function - DAAB EP104 Instruction Manual

Automatic control unit
Hide thumbs Also See for EP104:
Table of Contents

Advertisement

• Programmable inputs, P channels

There are six programmable inputs available in the EP104.
The instructions are identical for all six programmable inputs, apart from the channel number – input 1 has channel number
P1nn, input 2 has channel number P2nn, etc. The settings below are for input 1.
Activate input 1 by setting P100 to value 1.
The following channels are used to set the function for the programmable input.
P160, Control function
Option 0 disables the control function on the programmable input, 1 is for the opening function, 2 is for the closing function,
and 3 is for the stop function. Option 4 means open the gate if it is not already open, then close it as soon as it is in the
open position. Option 5 means open, stop and close alternately. Five seconds after the last command, the next command is
automatically set to open again.
P161, Type of control signal.
Use this channel to specify whether you want the signal to be a constant signal throughout the signal duration or just for the
on flank (the automatic control unit interprets the signal as a pulse). If the pulse option is set, hold-to-run does not work if the
safety edge is faulty but door can be operated via another input even if the input is activated.
P162, Half operation
To only open motor 1 set the value to 1, to only open motor 2 set the value to 2, and to open both motors 1 and 2 set the
value to 3.
P163, Limited opening
Set the value to 0 to open the door to its end position, or set it to 1 to open the door for the time set in C412 and/or C414
and L116/L126.
P170, Motor lock.
When the value is set to 1 the door will not start opening or closing before there is a signal at the input. This ensures that any
motor lock is raised before the door starts moving.
P175, Delayed opening
The motors will not start the opening until the input has been activated for the set time. This may be used, for example, to
prevent involuntary opening signals.
P180, Park
Use this channel to park the door. Option 0 disables the function, option 1 parks the door in the open position and waits for
a new control signal before the door is closed. To use a timer for parking and opening the door, set P160 to 1 and P180 to 2.
The input will then send a command to open the door in response to a signal, and keep the door open for as long as there is a
constant signal at the input.
P190, Interlock opening
Use this parameter with the value 1 if you want the input to open a local door and also forward the open signal to a remote
door.
P196, Blocking disabled for local and remote doors
Set the value to 1 to disable blocking for the local and remote doors.
P198, Automatic closing disabled for local and remote doors
Set the value to 1 to disable automatic closing for local and remote doors.

• Automatic closing

To prevent the door being left open, you can configure the unit to close it automatically after a specified period. You can choose
any time from 0.1 seconds to 9.59 minutes. The timer starts when the door stops moving. If any signal is received at a control
input, or if any safety device is activated in the closing direction, the timer is reset and starts recounting.
If you use automatic closing, it is a good idea to connect a wireless transmitter or a pull cord to an unused input. This is to
allow passing users to send a new open signal and reset the automatic closing time.
You can use programmable inputs and a timer to disable automatic closing at certain times of the day.

Configuring automatic closing

Select channel C500 for times between 0.00 and 9.59 minutes – the automatic closing time has an accuracy of 1 second.
Select channel C500 for times between 0.0 and 9.9 seconds – the automatic closing time has an accuracy of 0.1 second.
Channel C501 has precedence over C500, which means that the time set in C500 is ignored if C501 has a value greater
than 0.

Stop function

The automatic control unit has an adjustable stop function. The function applies to the normal stop buttons and also the
stop function in programmable inputs.
The initial setting is that when the stop button is pressed the countdown for automatic closing does not restart. If the door
is to always close automatically, even if a stop button has been pressed or after a current interruption, see 'Automatic closing'
28
DAAB AUTOMATIC CONTROL UNIT EP104
Bruksanvisning utgåva 1 för Programversion 4.06