Programmable Outputs, O Channels; Programmable Output 1 - DAAB EP104 Instruction Manual

Automatic control unit
Hide thumbs Also See for EP104:
Table of Contents

Advertisement

• Programmable outputs, o channels

Programmable output 1

No.
Name
o100
Function of output 1
0
Disabled
1
Position indication/Movement/Warning. Signal as configured in o110 – o122
2
Presence sensor/Direction sensing. Signal as configured in o191
3
Lock
4
Alarm output Signal as configured in o130 – o139
o110
Open position
0
Disabled
1
Constant signal
o111
Mid position
0
Disabled
1
Constant signal
o112
Closed position
0
Disabled
1
Constant signal
o113
Movement
0
Disabled
1
Constant signal in the opening movement
2
Constant signal in the closing movement
3
Constant signal in the opening and closing movement
4
No signal during movement, used in combination with o110, o111 and o112.
o114
Delayed switch-off Switch off after the specified
time For example to switch off lighting a specified
time after closing
o120
Warning time before start
o121
Warning function in combination with o120
1
Constant signal before park and automatic closing
2
Constant signal before close signal, park and automatic closing
3
Constant signal before all signals
o122
Function during warning time
1
Output signal deactivated during warning
2
Output signal as configured in o110-o113
o130*
Alarm if there is an error as configured in
o131-o139. The alarm is activated for at least the
time set in this channel.
o131*
Alarm for faulty safety edge. Time as in o130.
0
Disabled
1
Constant signal
* = Only when o100 is set to 4.
54
DAAB AUTOMATIC CONTROL UNIT EP104
Range
Factory Setting Ref.
0 - 4
1
0 - 1
1
0 - 1
0
0 - 1
0
0 - 4
4
0.00-9.59 minutes
0.00
0.00-9.59 minutes
0.00
1 - 3
1
1 - 2
1
0.00-9.59 minutes
0.00
0 - 1
0
Bruksanvisning utgåva 1 för Programversion 4.06