Stop Function With Run-On Time; Run-On Encoder; Setting Times For Timer Control; Reverse - DAAB EP104 Instruction Manual

Automatic control unit
Hide thumbs Also See for EP104:
Table of Contents

Advertisement

Stop function with run-on time

Select channel C436 and choose the stop function you want during the run-on time. The function specified in channel
C436 is only active during the run-on time for closing. Depending on the stop function configured in C436, you can set
the door to close tightly against rubber strips without triggering the load guard or safety edge.
NOTE! Channel C436 is subordinate to channel C448, safety edge reverse during the run-on time, see "Safety edge".
There are four options for the stop function during the run-on time in the closing movement – channel C436 0, 1, 2 or
3 – but safety edge reverse during the run-on time must be disabled in channel 448.

• Run-on encoder

See the "Stop function" section under "Run-on time" below. When using an encoder the run-on time is set by specifying how
many degrees of the cycle should be run-on. For these degrees of travel the safety edge and load guard can be disabled allowing
the door to be closed a bit extra. Set run-on using channels L117,L118,L127 and L128. Set the number of degrees for which
disengagement is to apply.
Stop function with run-on time
Select channel C436 and choose the stop function you want during the run-on time. The function specified in channel
C436 is only active during the run-on time for closing. Depending on the stop function configured in C436, you can set
the door to close tightly against rubber strips without triggering the load guard or safety edge.
NOTE! Channel C436 is subordinate to channel C448, safety edge reverse, during run-on time. See 'Safety edges.'
There are four options for the stop function during the run-on time in the closing movement – channel C436 0, 1, 2 or
3 – but safety edge reverse during the run-on time must be disabled in channel 448.

• Setting times for timer control

To set timer control instead of limit switch control, set L001 to 1.
Note that the limit switch inputs must be jumpered if timer control is enabled.
Run the barriers to fully open position, read the time in channel L211 for motor 1 and L221 for motor 2. Set the time for
motor 1 in channel L212 and for motor 2 in channel L222, add approx. 20% to the time. If timer control is enabled, note
that there must be some kind of mechanical stop to prevent the barrier opening or closing further than intended. The barrier
will reach its mechanical stop but the motor will continue running for the specified period.

• Reverse

Reverse delay

If necessary you can adjust the time taken by the door to change direction, for a faster or slower reverse.
Use channel C492 to configure the reverse delay – either opening or closing – after the photocell or a vehicle loop is
activated.
Select channel C492 and set a suitable delay.

Reverse priority

The automatic control unit is normally set to priority open, channel C063 = 1, which means that opening continues to the
fully open position even if the close button is pressed while the door is opening.
Important. The change of priority does not apply to the open/stop/close or open/close function in programmable inputs.
Priority open only
When the open button is pressed during closing, the direction changes to opening.
When the close button is pressed during opening, nothing happens.
Select channel C063 and set the value to 1.
Priority close only
When the close button is pressed during opening, the direction changes to closing.
When the open button is pressed during closing, nothing happens.
Select channel C063 and set the value to 2.
Priority open and close
When the open button is pressed during closing, the direction changes to opening.
When the close button is pressed during opening, the direction changes to closing.
Select channel C063 and set the value to 3.
No priority
Pressing the open or close button has no effect if the door is already moving.
Select channel C063 and set the value to 0.
30
DAAB AUTOMATIC CONTROL UNIT EP104
Bruksanvisning utgåva 1 för Programversion 4.06

Advertisement

Table of Contents
loading

Table of Contents