Figure 4.1-41 LN editing screen for SBO (for example)
Defining DIR setting mode
Figure 4.1-42 exemplifies the SPOS01 logic node saved as "GGIO1501". In the DIR mode, the
following three items should be selected using GR-TIEMS:
Figure 4.1-42 LN editing screen for DIR mode (for example)
Mapping output data
(ii)
The user should group the SPOS01 signals with regard to GOOSE and Report; the user should
map them for IEC 61850 communication using GR-TIEMS. Figure 4.1-43 illustrates how to
map a signal; it indicates that the signals for the SPOS01 function are required to be mapped
for IEC 61850 communication.
✓
SBOw
✓
Oper
✓
Cancel
✓
Origin
✓
stSeld
✓
sboClass† (choice "operate-once")
✓
ctlmodel (choice "SBOes or SBOns" )
†"sboClass" can be found by scrolling down.
✓
Oper
✓
origin
✓
ctlmodel (choice "DOes or DOns" )
- 663 -
6F2S1914 (0.49)
GRL200 (Soft 033 & 037)