Toshiba GR200 Series Instruction Manual page 703

Line differential protection ied
Hide thumbs Also See for GR200 Series:
Table of Contents

Advertisement

Receiving "Select command Open" by PLC function
(vi)
Figure 4.2-11 outlines the reception of the select command 'Open' by the PLC function.
Wait for a command
Select stage
Select command Closing from the remote-end
Select command Open from the remote-end
Select command Closing from the local-end
Select command Open from the local-end
Select command Closing by the PLC function
Select command Open by the PLC function
PLC logic programmed
by the user
Input signal from the PLC function
Figure 4.2-12 shows the select logic when a "Select command Open (PLC-Open-Control)" signal
is generated by the PLC function There are two input-points for the reception of this signal,
unlike in the signal "Select command Closing (PLC-Closing-Control)" where four are available.
That is, if interlock checking is required, use the connection point (PLC#1:e.g.,
DEV01_OP_INTERLOCK). Alternatively, if the interlock check is not required, use the
connection point (PLC#2:e.g., DEV01_OP_COMMAND). PLC#1 and the PLC#2 are shown in
Table 4.2-4.
Signals from user PLC logic
Open-control command requiring ILK checking
(PLC#1 connection point)
511001 800201EE31
DEV01_OP_INTERLOCK
ILK† condition ("Open") passed
DPSY01-Open
Open-control command requiring no ILK checking
(PLC#2 connection point)
511001 800201EE30
DEV01_OP_COMMAND
Figure 4.2-12 Select Open by PLC function in DPSY01
Note: To identify the input and output points of the DPSY02 logic, see Table 4.2-4 for
††
the inputs (PLC#1 and PLC#2) and Table 4.2-11 for the outputs.
Output signal to BO
Select logic
Figure 4.2-11 Outline of select command 'Open'
DPSY01 function (Function ID: 511001)
For DIR operation
Operation command
with ILK condition
For DIR operation
Operation command
without ILK condition
PLC in DIR operate
Select condition
- 680 -
Failed
Select
Signal output
decision
Success
Select logic in DPSY01
1≥
&
&
6F2S1914 (0.49)
Wait for a next command
Cancel logic
Cancel command
Cancel logic
Operate logic
Operate command
Operate logic
Output
&
To BO connection
"DPSY01_FSL_BO_CSF"
(511001_8A02011DC4)
0
t
Select "success"
0.1s
To "Wait for a command"
Select "Failed"
††
GRL200 (Soft 033 & 037)