Communication test
2.37.8
Local test (Local-test)
(i)
When setting [Local-test]=On, '1' is set for Local test bit of SCOM4 frame so that zero-ampere
control is executed at the remote end. The zero-ampere control is the one of test functions that
a local IED can treat the remote current data as zero.
a. IE EE C37.94 frame
Header
N=1
For example, during the test, suppose that setting [Local-test]=Off (as a default condition);
and CB and DSs are open at the local end. Remote CB can be tripped by the remote IED, if
currents are injected at the local IED while the communication is established between IEDs.
That is, the user needs to set [Local-test]=On for the test. Note that Test LED is lit while the
setting is On.
Local loop test (Loop-test)
(ii)
Suppose that GRL200s at local and remote ends are connected with TX and RX fiber optical
cables. If setting [Loop-test]=On, the user can have loop-back test at the local IED by disabling
sampling synchronization supervision function. Note other supervision functions are not
disabled, but there are following limitations during the test.
Sensitivity of DIF and DIFG elements becomes double. (If the injection of test current at
one terminal is 1A, the differential current Id becomes 2A.)
"Test LED" is On ("In service LED" is Off.)
Open test (OPEN 1/OPEN 2)
(iii)
If communication channels between IEDs should not be connected for testing, the user can cut
the channel when On is set setting [OPEN *]. For example, when setting [OPEN 1]=On, the
communication channel#1 will be cut at the local end. The default setting is Off.
I 0
Ia
V1
Figure 2.37-7 Location of local test bit
- 515 -
Ib
SCOM
Ic
COM1
SCOM1
SCOM2
MS0
MS1
SA0
RA0
RA1
SA1
MS0
MS1
SA2
RA3
RA4
SA3
MS0
MS1
SA4
Spare
Spare
SA5
MS0
MS1
SA6
RA0
RA1
SA7
MS0
MS1
SA8
RA3
RA4
SA9
MS0
MS1
SA10
Spare
Spare
SA11
6F2S1914 (0.49)
CRC
SCOM3
SCOM4
MS2
RA2
MS2
RA5
MS2
Spare
MS2
RA2
Local test
MS2
RA5
MS2
Spare
GRL200 (Soft 033 & 037)

Advertisement

Table of Contents
loading

Table of Contents