Actual-Frequency Monitoring (D008, P011, H004, H204); Torque Command Monitoring (D009, P033, P034); Torque Bias Monitoring (D010, P036 To P038); Torque Monitoring (D012) - Hitachi SJ700D-004L Instruction Manual

Sj700d-3 series
Hide thumbs Also See for SJ700D-004L:
Table of Contents

Advertisement

Chapter 4
4.1.8 Actual-frequency monitoring
The actual-frequency monitoring function is effective only when a motor
equipped with an encoder is connected to the inverter and the feedback option
board (SJ-FB) is mounted in the inverter. When the actual-frequency monitoring
function (d008) is selected, the inverter displays the actual operating frequency
of the motor (regardless of the motor control method (A044 or A244)).
(Display)
Forward operation:
0.00 to 99.99 in steps of 0.01 Hz-
100.0 to 400.0 in steps of 0.1 Hz
Note:
To use this monitoring function, set the encoder pulse-per-revolution (PPR) setting (P011) and the number of
motor poles (H004 or H204) correctly.
4.1.9 Torque command monitoring
The torque command monitoring function is effective when you have selected
control by torque for the vector control with sensor. When the torque
command monitoring function (d009) is selected, the inverter displays the
value of the currently input torque command.
The % monitor lamp lights up while the inverter is displaying the torque command value.
Assign 52 (ATR) on intelligent input terminal and turn on to activate torque control.
(Display)
0. to 200. in steps of 1 %
4.1.10 Torque bias monitoring
The torque bias monitoring function is effective when you have selected the
vector control with sensor. When the torque bias monitoring function (d010) is
selected, the inverter displays the value of the currently set value of torque bias.
The % monitor lamp lights up while the inverter is displaying the torque bias
value.
(Display)
-150. to +150. in steps of 1 %
4.1.11 Torque monitoring
When the torque monitoring function (d012) is selected, the inverter displays the
estimated value of the torque output from the inverter.
The % monitor lamp lights up while the inverter is displaying the estimated output torque.
(Display)
-300. to +300. in steps of 1 %
Note: This monitoring function is effective only when you have selected the sensorless vector control, 0Hz-range
sensorless vector control, or vector control with sensor as the control mode.
Displayed value is not accurate when the other control method is selected.
4.1.12 Output voltage monitoring
When the output voltage monitoring function (d013) is selected, the inverter
displays the voltage output from the inverter.
The V monitor lamp lights up while the inverter is displaying the output voltage.
(Display)
0.0 to 600.0 in steps of 0.1 V
(remark) Displayed value may not be accurate when the output voltage is differ from input voltage.
4.1.13 Power monitoring
When the power monitoring function (d014) is selected, the inverter displays the
electric power (momentary value) input to the inverter.
The kW monitor lamps (V and A lamps) light up while the inverter is displaying the input power.
(Display)
0.0 to 999.9 in steps of 0.1 kW
Explanation of Functions
Reverse operation:
0.0 to -99.9 in steps of 0.1 Hz
-100 to -400 in steps of 1 Hz
4-3
Related code
d008: Actual-frequency monitoring
P011: Encoder pulse-per-revolution (PPR)
setting
H004: Motor poles setting, 1st motor
H204: Motor poles setting, 2nd motor
Related code
d009: Torque command monitoring
P033: Torque command input selection
P034: Torque command setting
A044:
V/f characteristic curve selectcion
C001 to C008: Terminal [1] to [8] functions
Related code
d010: Torque bias monitoring
A044:
V/f characteristic curve selectcion
P036: Torque bias mode
P037: Torque bias value
P038: Torque bias polarity
Related code
d012: Torque monitoring
A044:
V/f characteristic curve selectcion
Related code
d013: Output voltage monitoring
Related code
d014: Power monitoring