■Data line
Column name
Date column
Event number column
Event name column
Occurrence type column
Occurrence comment column
*2*3*4
Monitoring data value column
*1 When a file is opened in Excel, the date column format is displayed in the default setting of Excel.
Set the cell format as necessary.
(Example) To display year, month, date, hour, minute, second, and millisecond information
Specify the user defined display format as follows:
yyyy/mm/dd hh:mm:ss.000
*2 If the device data value specified with monitoring data cannot be represented with the type specified for "Data type", "NaN" is output in
the data line.
*3 When the monitoring data value is string type data, among Unicode Basic Multilingual Plane, control character codes of U+0000 to
U+001F, U+007F to U+00A0, U+00AD, and linefeed code of U+2028 and U+2029 are replaced with period (.).
For CSV file, characters outside the ASCII range, double quotes ("), comma (,), and semicolon (;) are replaced with period (.).
If a string terminator (0) is used halfway in the data, the data is output without replacing a string terminator (0) with period (.), and the
subsequent data is not output.
*4 The content is not output when the number of units of data is '0'.
*5 In the underlined part, the information of set amount of event condition is output delimited by a semicolon (;).
*6 In the underlined parts, the information of start condition, end condition, and count condition is output delimited by a semicolon (;).
The data line size is calculated as shown below. For a CSV file, replace the number of tabs with the number of commas, and
divide the total size by 2.
For event logging of the word [unsigned]/bit string [16-bit] decimal format 0 digit data
(Date column: YYYY/MM/DD hh:mm:ss.s, event name length: 10, occurrence comment length: 4, monitoring data value
column (single condition): "D12000 = -23456")
Data line size
= 42 [date column] + 4 [event number column] + 20 [event name column] + 2 [occurrence type column]
+ 8 [occurrence comment column] + 26 [monitoring data value column] + 10 [number of tabs] + 4 [CR+LF]
= 116 [bytes]
Output content
Outputs data according to the data line output format specified in the Unicode text
*1
output setting/CSV output setting.
(Example) 2016/1/15 10:15:20
Outputs the number of the event 1 to 256 which occurred or was restored.
If the event type is "At module startup", '0' is output.
Outputs the name of the event which occurred or was restored.
If the event type is "At module startup", 'RD81DL96 Start' is output.
Outputs the type of event which occurred or was restored.
When occurred : '1'
When restored : '0'
If the event type is "At startup of module", '1' is output.
Outputs the comment at event occurrence/comment at event restoration set in the
"Event setting" screen.
The content is not output when the event type is "At startup of module". (Outputs tab
or comma immediately after the tab or comma.)
The monitoring data value at occurrence/restoration is output in the following format.
• For a single condition
'(Data name) = (Monitoring data value)'
• For a compound condition (comparison)
'(Data name) = (Monitoring data value)'
• For a compound condition (number of times)
'Count = (Count value); (Data name) = (Monitoring data value)'
• For a compound condition (order)
'(Completion information); (Data name) = (Monitoring data value)'
Outputs any of the following data in the completion information.
When normal pattern is detected: 'Complete'
When abnormal pattern or timeout is detected: 'Phase=[condition location]'
The condition number which detected the abnormal pattern or timeout is output to
condition location.
1: 1st condition
2: 2nd condition
3: 3rd condition
When the event type is "At module startup", nothing is output. (CR+LF is output
immediately after the tab or a comma.)
*5
*6
*6
Appendix 10 Event Logging File Format
Size (bytes)
Unicode
CSV
2 to 64
1 to 32
(Depends on
(Depends on
Unicode text
CSV output
output
setting)
setting)
2 to 6
1 to 3
2 to 64
1 to 32
2
1
2 to 64
1 to 32
0 to 33288
0 to 16644
APPX
367
A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-rd81dl96Melsec iq-sw1dnn-rdlutl

Table of Contents