Error code
Error name
1E83H to 1E84H
High speed sampling setting
illegal error
1E89H
Device name error
1E8BH
Module error
1E91H
Module error
1E97H to 1E9AH
High speed sampling
unsupported CPU error
1E9BH
High speed sampling overlap
error
1E9CH to 1E9DH
Module error
1EA6H
High speed sampling
unsupported CPU error
1EBBH to
Module error
1EBCH
1EC5H to 1EC6H
Setting file error
1ED0H to 1ED5H
Device name error
1ED6H
Device error
1ED7H
Module error
1F05H
Module error
Error description
An invalid "High speed sampling setting" was
configured.
Or the setting file is corrupted.
The device name specified in the "Data logging
setting", "Event logging setting", or "Report
setting" is incorrect.
Or an invalid device was specified.
A module error has been detected.
A module error has been detected.
The control CPU does not support high speed
sampling.
Another intelligent function module is performing
high speed sampling.
A module error has been detected.
The control CPU does not support high speed
sampling.
A module error has been detected.
There is no setting file.
Or the setting file is corrupted.
The device name specified in the "Data logging
setting", "Event logging setting", or "Report
setting" is incorrect.
Or an invalid device was specified.
An incorrect device is specified.
A module error has been detected.
A module error has been detected.
Corrective action
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Correct the device name specified in the "Data
logging setting", "Event logging setting", or
"Report setting".
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in high speed data logger
module. Please consult your local Mitsubishi
representative.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in high speed data logger
module. Please consult your local Mitsubishi
representative.
• Replace it with a CPU that supports high speed
sampling.
■Execute either of the followings and cycle the
power or reset the CPU module to restart the
module.
• Specify general data sampling and write the
settings.
• Stop high speed sampling on the other
intelligent function module.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in high speed data logger
module. Please consult your local Mitsubishi
representative.
• Replace it with a CPU that supports high speed
sampling.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in high speed data logger
module. Please consult your local Mitsubishi
representative.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Correct the device name specified in the "Data
logging setting", "Event logging setting", or
"Report setting".
• Correct the set device.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in high speed data logger
module. Please consult your local Mitsubishi
representative.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in high speed data logger
module. Please consult your local Mitsubishi
representative.
4 TROUBLESHOOTING
4.4 Error Code List