Error code
Error name
1D50H to 1D54H
Module error
1D56H
Setting file error
1D57H
Setting file error
1D80H to 1D83H
SD memory card mount failed
1D90H to 1D93H
Module error
1D94H
SD memory card format error
1D95H
SD memory card check error
1D96H
SD memory card response error
1D97H
SD memory card drive error
1DA0H
SD memory card mount failed
1DA1H to 1DA4H
Module error
1DD0H
SD memory card access error
1DD1H
SD memory card response error
1E00H
SD memory card access error
1E01H
SD memory card access error
1E02H
SD memory card access error
1E03H
SD memory card access error
1E70H to 1E71H
Module error
4 TROUBLESHOOTING
278
4.4 Error Code List
Error description
A module error has been detected.
There is no setting file.
Or the setting file is corrupted.
The high speed data logger module version is
older than the setting file version.
The SD memory card mount is failed because a
failure was detected.
A module error has been detected.
Failed to format the SD memory card.
Failed to check the SD memory card.
Access to the SD memory card timed out while
waiting for a response from the card.
The SD memory card mount is failed because a
failure was detected.
Or the SD memory card drive is in error status
because the SD memory card was ejected during
file access.
The SD memory card mount is failed because a
failure was detected.
A module error has been detected.
An error occurred when accessing the file.
Access to the SD memory card timed out while
waiting for a response from the card.
The access to the SD memory card was
attempted when the file access was being
stopped.
Access to the SD memory card was attempted
with no card installed.
The access to the unformatted SD memory card
was attempted.
The access to the SD memory card was
attempted while it is being formatted.
A module error has been detected.
Corrective action
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in high speed data logger
module. Please consult your local Mitsubishi
representative.
• Write the settings again with the Configuration
Tool.
• Replace the SD memory card.
• Start the Configuration Tool online from the high
speed data logger module to be used and write
the settings.
• Check if the SD memory card was inserted
properly.
• Replace the SD memory card.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in high speed data logger
module. Please consult your local Mitsubishi
representative.
• Check if the SD memory card was inserted
properly.
• Replace the SD memory card.
• Replace the SD memory card.
• Replace the SD memory card.
• Cycle the power of the system where the high
speed data logger module is mounted or reset
the CPU module.
• Stop file access, then remove the SD memory
card.
• Check if improper files of folders exist in the SD
memory card.
• Check if the SD memory card was inserted
properly.
• Replace the SD memory card.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in high speed data logger
module. Please consult your local Mitsubishi
representative.
• Check if the SD memory card was inserted
properly.
• Replace the SD memory card.
• Check if the SD memory card was inserted
properly.
• Replace the SD memory card.
• Turn the clear file access stop request (Y3) ON,
and retry after the file access status (X2) is
turned OFF.
• Access after inserting a SD memory card.
• Access after formatting the SD memory card.
• Access after formatting the SD memory card.
• Take measures to reduce noise.
• Reset the CPU module and switch it to RUN. If
the same error is displayed again, a hardware
failure may occur in high speed data logger
module. Please consult your local Mitsubishi
representative.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec iq-rd81dl96Melsec iq-sw1dnn-rdlutl

Table of Contents