High speed sampling failure (X1A)
This signal turns ON when high speed sampling failure occurs in data logging, event logging or report. (Page 344
Processing Time)
This signal turns OFF by updating the settings.
Processing overload occurrence (X1B)
This signal turns ON when a processing overload occurs in data logging, event logging or report. (Page 344 Processing
Time)
This signal turns OFF by updating the settings.
Trigger reoccurrence (X1C)
This signal turns ON when trigger reoccurs in data logging. (Page 344 Processing Time)
This signal turns OFF by updating the settings.
Creation trigger reoccurrence (X1D)
This signal turns ON when trigger reoccurs in report. (Page 344 Processing Time)
This signal turns OFF by updating the settings.
General sampling delay occurrence (X1E)
This signal turns ON when a general sampling delay occurs in data logging, event logging, or report. (Page 344
Processing Time)
This signal turns OFF by any of the following operations.
• Updating the settings
• Setting a value more than the general sampling delay time (maximum) in the 'allowed general sampling delay time'
(Un\G804 to 805).
APPX
Appendix 2 Input/Output Signals
A
297