HGM9560 BUS TIE MAINS PARALLEL UNIT

11.2 MAINS CONTROL MODE

If the power value is set as a positive number, when the mains input increases above the power
setpoint, the generator bus will supply the extra load in order to maintain the mains input at the
predefined level (mains peak lopping mode).
If the power value is set as a negative number, the generator bus will supply the preset power to
mains. The total output power of the generator bus is the sum of the consumption power and the
preset power which supplied by generator bus to mains.
Mains Peak Lopping:
HGM9560 Bus Tie Mains Parallel Unit
ISSUE 2013-12-30
Version 1.0
Page 41 of 51