6.3 FUNCTION DESCRIPTION FOR DIGITAL INPUT PORTS

No.
Input Ports
0
Not used
1
Emergency stop
Start Inhibit
2
Low pipe pressure
3
4
Reserved
5
Reserved

6.4 FUNCTION DESCRIPTION FOR DIGITAL OUTPUT PORTS

No.
Output Ports
0
Not used
Pipe control output
1
Alarm Output
2
OFF Mode Output
3
Auto Mode Output
4
Manual Mode Output
5
Reserved
6
Reserved
7
Reserved
8
Reserved
9

7 OPERATIONS

7.1 OFF MODE

Press OFF key
mode.
In this mode, the pump controls the relay to stop output.

7.2 AUTO MODE

Press the Auto key
Auto mode.
In this mode, when the AC power is normal, and the overload input/emergency stop input/start
inhibit is inactive, the relay outputs when the sensor pressure value is lower than low start threshold
value, and the pump controls relay to stop output when the value is higher than the start return
threshold value.
FPC1700 Jockey Pump Controller User Manual
Table 10 Function Description for Input Port
The input port is inactive.
The start relay will stop output when emergency input is active.
The start relay will stop output when the start input inhibit is
active.
When sensor curve type is set to not used, the start relay will
output when low pipe pressure is active.
Reserved
Reserved
Table 11 Function Description for Output Port
The output port is inactive.
The relay will output when starts or stops.
The relay will output when alarms.
The relay will output in OFF mode.
The relay will output in Auto mode.
The relay will output in Manual mode.
保留 Reserved
保留 Reserved
保留 Reserved
保留 Reserved
, the indicator light of OFF mode is illuminated and the controller is in OFF
, the indicator light of Auto mode is illuminated and the controller is in
Description
Description
Page 13 of 17