12. OPERATION OF EACH SPECIAL MODULE MONITOR SCREEN

12.17.3 Graph monitor

1)
2)
No.
The current input value, a value between 0 to 4000 for the digital input value
1)
of each channel, is displayed in a graph as a percentage ranging from 0 to
100%.
The set D/A conversion enabled/disabled status for each channel is
displayed.
2)
The set analog output enabled/disabled status for each channel is displayed.
A "!" is displayed when a watchdog timer error occurs.
For A616DAI:
A "!" is displayed when the digital input value of any channel is set to 4096
3)
or higher, or to a negative number.
For A616DAV:
A "!" is displayed when the digital input value of any channel is set to 4096
or higher, or to -4097 or lower.
Contents of display
12 - 49
GOT
MELSEC
Buffer memory address to
reference (hexadecimal)
10 to 1F
0
1
3)