Position units

Function not active
Function active
10.7.

Process factor units

Display M0009
Temperature unit M0052
Default value: °C
Setting range: °C or °F
The valve position (e.g. actual position, setpoint position, ...) or other positions (e.g.
pivot points) are indicated in percent of the travel in the actuator controls controls
display (default setting). By activating parameter Position, you may select other
physical units instead of percent to represent the positions. Furthermore, both scaling
and maximum value may be adapted. The change-over affects all screens indicating
a position. This includes status pages such as S0001 S0003, but also the
representation of characteristics (e.g. position-time) as well as histograms.
Activate position unit
Required user level: Specialist (4) or higher.
Display M0009
Units M1205
Position M1206
Position activation M1207
Default value: Function not active
Setting values:
<Units of position> function deactivated. Position indications in the display (e.g. the
valve position S0001) are indicated in percent.
<Units of position> function activated. Position indications in the display are not
shown in percent but in the unit set for the values in parameter group Position.
Set max. value, scaling and unit
Required user level: Specialist (4) or higher.
Display M0009
Units M1205
Position M1206
Max. value at 100.0 % M1208
Scaling M1209
Unit M1210
Default values:
Max. value at 100.0 % = 1000
Scaling = 1
Unit = mA
Setting ranges/values:
Max. value at 100.0 % = 1 – 1000
Scaling = 0.001 – 1000 (multiplier factor for unit)
Unit = mA; °C; bar; m³/h; m³/min; m; cm; mm; °
Process factors (e.g. process setpoint, actual process value, ...) are shown in percent
of travel on the actuator controls controls display (default setting). By activating the
parameter Process factor, you may select other physical units apart from percent.
The change-over affects all screens indicating a process value.
Activate process factor units
Required user level: Specialist (4) or higher.
Display M0009
Display formats
49