Operation mode EMERGENCY

Properties
7.5.

Operation mode Disabled

Properties
36
In direction OPEN = self-retaining (in direction CLOSE push-to-run operation):
After an operation command in direction OPEN, the actuator continues to run, even
if the operation command is cancelled (self-retaining). The actuator is either stopped
by the STOP command or if end position OPEN or an intermediate position OPEN
has been reached.
In direction CLOSE = self-retaining (in direction OPEN push-to-run operation):
After an operation command in direction CLOSE, the actuator continues to run, even
if the operation command is cancelled (self-retaining). The actuator is either stopped
by the CLOSE command or if end position CLOSED or an intermediate position
CLOSED has been reached.
In directions OPEN and CLOSE = self-retaining:
After an operation command, the actuator continues to run in directions OPEN or
CLOSE, even if the operation command is cancelled (self-retaining). The actuator
is either stopped by the STOP command or if an end position or intermediate position
has been reached.
Direct reversal of operation is not possible. Operation commands in directions OPEN
or CLOSE must be stopped first by the STOP command. Only then is an operation
command into the opposite direction allowed.
In directions OPEN and CLOSE = self-retaining without stop:
Direct reversal of operation without STOP command is possible.
Direct reversal of operation is also possible without STOP command. However,
operation can be stopped at any time by the STOP command.
See also: Failure function <EMERGENCY behaviour>
The indication in the top line of the display shows:
The operation mode EMERGENCY is initiated by the EMERGENCY signal.
The actuator performs a defined EMERGENCY operation. For example, the
actuator travels to a predefined EMERGENCY position (i.e. end position OPEN
or end position CLOSED).
As long as the EMERGENCY signal is present, the actuator does not respond
to any other operation commands (EMERGENCY signal has top priority).
The actuator can start immediately when switching on!
Risk of personal injuries or damage to the valve.
Ensure that the EMERGENCY input is not activated when switching on. This
means connect the EMERGENCY signal appropriately.
Actuators with magnetic pen control panel: If the actuator starts unexpectedly:
tap OFF with the magnetic pen.
Actuators with Combi-Switch: If the actuator starts unexpectedly: immediately
turn selector switch to position OFF.
If the actuator starts unexpectedly and parameter EMCY operation mode equals
Remote, Local and Off: immediately disconnect from mains.
See also: Application function <Local controls: enable>
The indication in the top line of the display shows:
Operation via the local controls is disabled.