Application functions
12.4.7.

Closing fully/opening fully (end position tolerance for setpoint)

12.4.8.

Limit setting range

Function not active
Function active
Parameter
64
If the end positions cannot be reached due to inaccurate analogue setpoint signals
(0/4 mA or 20 mA), a tolerance for the setpoint within the end position range can be
set. If the tolerance is exceeded or not reached, the actuator continues the operation
until the full end position has been reached. This ensures that the actuator opens
and closes fully.
Customer settings M0041
Positioner M0145
Tolerance CLOSE M0150
Tolerance OPEN M0151
Default values:
Tolerance CLOSE = 0.0 %
Tolerance OPEN = 100.0 %
Setting ranges: (in percent of the travel)
Tolerance CLOSE = 0.0 – 5.0 %
Tolerance OPEN = 95 – 100.0 %
Setting range can be limited in directions OPEN and/or CLOSE.
This prevents end position(s) OPEN and/or CLOSED from being approached in
modulating duty. The actuator stops when reaching the set limit value.
For OPEN-CLOSE control (LOCAL or REMOTE OPEN-CLOSE operation mode),
this limitation is not active. The valve can then be run into the end positions either
via the local controls or from remote.
Figure 52: Limitation of setting range
[1]
Permissible actuator travel for setpoint control
[2]
Permissible actuator travel for OPEN-CLOSE control
Activate limitation
Customer settings M0041
Positioner M0145
Limit setting range M0845
Default value: Function not active
Setting values:
Limitation deactivated.
Limitation activated.
Adjust setting limits
Customer settings M0041
Positioner M0145
Limit OPEN M0162
Limit CLOSE M0161
Default values: