Advertisement

Application functions
Information
12.4.

Positioner (operation mode REMOTE SETPOINT)

Requirements
Properties
Information
Parameters
Table 7:
Display text
Adaptive behaviour
Outer dead band
Dead time
Dead band OPEN
Dead band CLOSE
Posit. hyst. OPEN
Posit. hyst. CLOSE
Tolerance OPEN
Tolerance CLOSE
Limit setting range
Limit OPEN
58
Hysteresis 1 M0277
Default values: 0.5 % for all 8 positions
Setting range:0.0 % to 5.0 % of the travel (from OPEN to CLOSED)
For signal behaviour D, the value XT (parameter Outer dead band M0148) determines
pulse duration pT and influences switch-on point P1.
The positioner records setpoint position E1 and actual position value E2 and compares
both. Depending on the detected deviation, the actuator motor is then controlled in
directions OPEN or CLOSE.
If the actuator is controlled via a setpoint (e.g. 0
S0003 on the display shows both setpoint position E1 and actual position value
E2.
If the status indication S0003 only shows the actual position value E2, OPEN-
CLOSE control is active and there is no setpoint control via the positioner. In
this case, you have to change-over to setpoint control first, refer to <Change-
over between OPEN-CLOSE control and setpoint control> chapter.
The menu item Positioner is used to set the following parameters:
Menu ID
M0147
M0148
M0149
M0234
M0235
M0598
M0599
M0151
M0150
M0845
M0162
PRM
PRM_0084
PRM_0087
PRM_0086
PRM_0212
PRM_0213
PRM_2916
PRM_2917
PRM_0214
PRM_0215
PRM_4167
PRM_0222
Multi-turn actuators
TR-M30X
TR-M1000X
20 mA), the status indication
Signification
Setting options:
Off or Adaptive I
Setting the outer dead band (only
in combination with adaptive beha-
viour = Off)
Setting the dead time
Setting dead band OPEN (only in
combination with adaptive beha-
viour = Off)
Setting dead band CLOSE (only in
combination with adaptive beha-
viour = Off)
Setting positioner hysteresis OPEN
(only in combination with adaptive
behaviour = Adaptive I)
Setting positioner hysteresis
CLOSE (only in combination with
adaptive behaviour = Adaptive I)
Tolerance for the "Opening fully"
function for end position OPEN
Tolerance for the "Closing fully"
function for end position CLOSED
Limit setting range function act-
ive/not active If necessary, the
setting range can be limited in dir-
ections CLOSE and OPEN. This
prevents end position(s) OPEN
and/or CLOSED from being ap-
proached in modulating duty.
When reaching the modulating
limit OPEN and CLOSE, the actu-
ator will stop. For operation mode
LOCAL or REMOTE OPEN-
CLOSE, this limitation is not active.
Set limit OPEN.
Default value: 100 %