Example
Information
13.5.1.

Activate Interlock

Function not active
Function active
13.5.2.

Set source of the Interlock enable signal

Active comm. source
Interface
Fieldbus
13.5.3.

Operation mode for Interlock

Off
Device configuration M0053
I/O interface M0139
Digital inputs M0116
Use input DIN 5 to enable operation commands in direction CLOSE:
Parameters: Signal DIN 5 M0122
Setting value: Enable CLOSE
The logic for the digital inputs may be inverted. Depending on the parameter setting
(e.g. Coding DIN 5M0127), the input is either High active or Low active. Default setting
is High active.
Enable/disable commands via digital input
Switching behaviour for coding High active:
Enable OPEN bzw. Enable CLOSE inpu t= low level (0 V DC or input open):
Operation command is enabled.
Enable OPEN or Enable CLOSE input = high level (default: +24 V DC):
Operation command disabled.
Required user level: Specialist (4) or higher.
Device configuration M0053
Application functions M0178
Activation M0212
Interlock M0663
Default value: Function not active
Setting values:
Function <Interlock (enable operation commands)> deactivated.
Function <Interlock (enable operation commands)> activated.
Customer settings M0041
Interlock M0664
Interlock source M1013
Default value: Active comm. source
Setting values:
Signals for enabling operation commands are sent via the active interface. I.e.
changing the command source also changes the failure source of the enable signal.
The enable signal for the operation commands must be configured as binary signal
(default: +24 V DC) at a digital input (parameter: Enable OPEN/Enable CLOSE).
Actuators with fieldbus or communication interface: The enable signal for the
operation commands must be triggered by the fieldbus Interlock OPEN or Interlock
CLOSE commands.
The additional enable signal can be activated for different operation modes.
Customer settings M0041
Interlock M0664
Oper. mode Interlock M0665
Default value: Off both directions
Setting values:
Interlock is switched off.
Failure functions