Commissioning

38
9
Commissioning
9.1

Preliminaries

The measuring range and the unit in which the measured value is transmitted correspond
to the data on the nameplate.
WARNING
L
The settings of the current output are relevant for safety!
This situation can result in product overflow.
The setting of the current output depends on the setting in the Assign PV parameter.
After changing the Assign PV parameter, check the settings for the range (LRV and
URV) and reconfigure them if necessary.
WARNING
L
Process pressure above or below permitted maximum/minimum!
Risk of injury if parts burst! Warnings are displayed if the pressure is too high.
If a pressure smaller than the minimum permitted pressure or greater than the
maximum permitted pressure is present at the device, a message is output.
Only use the device within the measuring range limits!
9.1.1
As-delivered state
If no customized settings were ordered:
• Assign PV parameter Pressure option
• Calibration values defined by defined measuring cell nominal value
• The alarm current is set to min. (3.6 mA), (only if no other option was selected when
ordering)
• DIP switch to Off position
• If Bluetooth is ordered, then Bluetooth is switched on
9.2

Function check

Perform a function check before putting the measuring point into operation:
• "Post-installation check" checklist (see the "Installation" section)
• "Post-connection check" checklist (see the "Electrical connection" section)