Soliwave FDR56/FQR56
Endress+Hauser
Press the button on the device to configure the desired signal strength
→ Display of the changed simulated signal strength, example: signal strength = 8
LEDs, switch output: switched, current output: 16.8 mA
Move the encoding switch to the initial position 0
→ Display of the current signal strength
The simulation ends as soon as the encoding switch is no longer at position 9.
7.4
Overview device functions
Function
Description
0
Display of the signal strength
1
Automatic adjustment with free path
2
Automatic adjustment with covered path
3
Manual adjustment with free path
4
Manual adjustment with covered path
5
Hysteresis
6
Limit signal function
7
Switch-on delay
8
Switch-off delay
9
Simulation
A
Damping
B
Without fuction
C
Without fuction
D
Without fuction
E
Without fuction
F
Reset to factory settings
8
Commissioning
8.1
Function check
Before commissioning the measuring point, check whether the post-installation and post-
connection checks have been performed.
• "Post-installation check" checklist → 21
• "Post-connection check" checklist" → 26
8.2
Powering up the measuring device
The microwave barrier will be switched on by an applied power supply on FQR56 trans-
mitter and FDR56 transceiver.
The microwave barrier is ready for operation a maximum of 3 s after the supply voltage is
applied.
Commissioning
Factory settings
―
―
―
―
―
―
―
―
―
―
―
35