Lenovo Flex System x440 Compute Node Installation And Service Manual page 594

Table of Contents

Advertisement

User Response
Complete the following steps:
1. Check the CMM or FSM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are
in place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. Make sure that the DIMM baffles are in place.
5. If the problem persists and there are no other DIMMs with the same indication, replace the
DIMM.
• 806f0a13-2401ffff : A Fatal Bus Error has occurred on bus [SensorElementName].
A fatal bus error has been detected on the System Management Bus.
May also be shown as 806f0a132401ffff or 0x806f0a132401ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Other
SNMP Trap ID
50
CIM Information
Prefix: PLAT ID: 0244
User Response
This is a UEFI detected event. The UEFI diagnostic code for this event can be found in the logged
IMM message text. Please refer to the UEFI diagnostic code in the "UEFI diagnostic code" section of
the Information Center for the appropriate user response.
Related links
Finding the UEFI diagnostic code
• 806f0a13-2582ffff : A Fatal Bus Error has occurred on bus [SensorElementName].
IMM has detected a Bus Fatal Error relating to PCI.
May also be shown as 806f0a132582ffff or 0x806f0a132582ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Other
Lenovo Flex System x440 Compute NodeInstallation and Service Guide