Lenovo Flex System x440 Compute Node Installation And Service Manual page 299

Table of Contents

Advertisement

– If the specified sensor is Planar 12V, check the Chassis Management Module or Flex System
Manager event log for power-supply-related issues, and resolve those issues. If the problem
remains, replace the system board.
• 80010b01-3701ffff : Numeric sensor Inlet 1 Temp going high (upper non-recoverable) has asserted.
has asserted.
The inlet temperature has exceeded its specified threshold. The compute node has initiated a hard
shutdown.
May also be shown as 80010b013701ffff or 0x80010b013701ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0498
User Response
Complete the following steps until the problem is solved:
1. Check the Chassis Management Module or Flex System Manager event log for any fan- or
cooling-related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are
in place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
• 80010b01-3702ffff : Numeric sensor Inlet 2 Temp going high (upper non-recoverable) has asserted.
The inlet temperature has risen above the specified threshold. The system has initiated a hard shutdown.
May also be shown as 80010b013702ffff or 0x80010b013702ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0498
.
Chapter 6
Troubleshooting
289