Lenovo Flex System x440 Compute Node Installation And Service Manual page 593

Table of Contents

Advertisement

• 806f0a0c-202fffff : An Over-Temperature Condition has been detected on the
[PhysicalMemoryElementName] on Subsystem [MemoryElementName].
An over temperature condition for memory has been detected.
May also be shown as 806f0a0c202fffff or 0x806f0a0c202fffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0146
User Response
Complete the following steps:
1. Check the CMM or FSM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are
in place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. Make sure that the DIMM baffles are in place.
5. If the problem persists and there are no other DIMMs with the same indication, replace the
DIMM.
• 806f0a0c-2030ffff : An Over-Temperature Condition has been detected on the
[PhysicalMemoryElementName] on Subsystem [MemoryElementName].
An over temperature condition for memory has been detected.
May also be shown as 806f0a0c2030ffff or 0x806f0a0c2030ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0146
.
Chapter 6
Troubleshooting
583

Advertisement

Table of Contents
loading

This manual is also suitable for:

71672590

Table of Contents